10kV Dry-type Transformer
10kV Dry-type Transformer
10kV Dry-type Transformer
10kV Dry-type Transformer
10kV Dry-type Transformer
+
  • 10kV Dry-type Transformer
  • 10kV Dry-type Transformer
  • 10kV Dry-type Transformer
  • 10kV Dry-type Transformer
  • 10kV Dry-type Transformer

10kV Dry-type Transformer

● Model: SC(B)12、SC(B)14、SC(B)18 ● Capacity: 30kVA to 2500kVA ● Voltage: 0.4kV, 6kV to 11kV

Categories:

Dry-type Transformer

Product Overview 

SC(B) series epoxy casting dry-type transformer produced by Ruier Electric is a kind of mechanical strength, electrical strength, heat-resistant dry-type transformer with filler F-class epoxy resin mixture, after vacuum film degassing, under vacuum and pressure, thin-layer casting inside and outside the surface of the high and low voltage coils reinforced by glass wire molding network, presenting a kind of mechanical strength, electrical strength, heat-resistant degree of dry-type transformer is very high. Ruier Electric adopts advanced production equipment, assured raw materials, scientific management, advanced technology, strict testing methods, so that the quality and performance of the products to reach the international level.

Application Scene 

  1. Epoxy dry-type transformers are suitable for a wide range of applications, including indoor and outdoor installations. They are typically used in commercial and industrial environments such as hospitals, data centers and factories. Specific application scenarios include:
  2. Urban power grids: as a replacement for oil-immersed distribution transformers.
  3. High-rise buildings: Installed in load centers to provide a stable power supply.
  4. Commercial centers: suitable for places with high environmental requirements, avoiding oil pollution and noise interference.
  5. Hospitals, theaters, hotels: provide safe and reliable power supply.
  6. Tunnels, subways, underground power stations: suitable for high humidity and harsh environments.
  7. Chemical plants, nuclear power plants: suitable for places with high requirements for safety and reliability.

Product Overview 

Model number

Rated capacity
(kVA)

 Voltage Combination

Linkage group

 labeling

Impedance voltage


(%)

Transformer weight
(kg)

Transformer reference size(mm)
L*W*H

Housing reference size(mm)
L*W*H

No-load loss
(w)

Load Loss
(w)

High Voltage(kV)

Low Voltage (kV)

SC12-30

  30 

6

6.3

10

10.5

0.4

Dyn11

YynO

0.25 

680*450*640

1100*850*1040

150 

710 

SC12-50

  50 

0.3 

700*450*640

1260*850*1150

215 

1000 

SC12-80

  80 

0.43 

860*450*760

1500*1300*2200

295 

1380 

SC12-100

100 

0.63 

920*780*900

1500*1300*2200

320 

1570 

SC12-125

125 

0.7 

920*780*950

1500*1300*2200

375 

1850 

SC12-160

160 

0.8 

920*780*1000

1800*1300*2200

430 

2130 

SC12-200

200 

0.95 

1100*780*1000

1800*1300*2200

495 

2530 

SC12-250

250 

1.1 

1100*650*1150

1800*1300*2200

575 

2760 

SC12-315

315 

1.3 

1100*940*1150

1800*1300*2200

705 

3470 

SCB12-400

400 

1.5 

1100*940*1200

2000*1500*2200

785 

3990 

SCB12-500

500 

1350*940*1200

2000*1500*2200

930 

4880 

SCB12-630

630 

205 

1350*940*1300

2000*1500*2200

1070 

5880 

SCB12-630

630 

205 

1400*940*1130

2000*1500*2200

1040 

5960 

SCB12-800

800 

2.35 

1450*940*1140

2000*1500*2200

1215 

6960 

SCB12-1000

1000 

2.75 

1500*940*1250

2000*1600*2200

1415 

8130 

SCB12-1250

1250 

3.1 

1500*940*1300

2000*1600*2200

1670 

9690 

SCB12-1600

1600 

3.6 

1500*940*1410

2200*1600*2200

1960 

11730 

SCB12-2000

2000 

4.6 

1650*1190*1780

2200*1600*2200

2440 

14450 

SCB12-2500

2500 

5.5 

1720*1190*1800

2200*1600*2200

2880 

17170 

SC(B)12  epoxy casting dry-type transformer

 

Model number

Rated capacity
(kVA)

 VoltageCombination

Linkage group

 labeling

Impedance voltage


(%)

Transformer weight
(kg)

Transformer reference size

(mm)
L*W*H

Housing reference size(mm)
L*W*H

No-load loss
(w)

Load Loss
(w)

High Voltage(kV)

Low Voltage (kV)

SC14-30

30 

6

6.3

10

10.5

0.4

Dyn11

YynO

0.28 

680*450*640

1100*850*1040

130 

640 

SC14-50

50 

0.33 

700*450*640

1260*850*1150

185 

900 

SC14-80

80 

0.47 

860*450*760

1500*1300*2200

250 

1240

SC14-100

100 

0.7 

920*780*900

1500*1300*2200

270 

1415 

SC14-125

125 

0.77 

920*780*950

1500*1300*2200

320 

1665 

SC14-160

160 

0.88 

920*780*1000

1800*1300*2200

365 

1915 

SC14-200

200 

1.03 

1100*780*1000

1800*1300*2200

420 

2275 

SC14-250

250 

1.2 

1100*650*1150

1800*1300*2200

490 

2485 

SC14-315

315 

1.43 

1100*940*1150

1800*1300*2200

600 

3125 

SCB14-400

400 

1.65 

1100*940*1200

2000*1500*2200

665 

3590 

SCB14-500

500 

2.1 

1350*940*1200

2000*1500*2200

790 

4390 

SCB14-630

630 

2.25 

1350*940*1300

2000*1500*2200

910 

5290 

SCB14-630

630 

2.25 

1400*940*1130

2000*1500*2200

885 

5365 

SCB14-800

800 

2.6 

1450*940*1140

2000*1500*2200

1035 

6265 

SCB14-1000

1000 

3

1500*940*1250

2000*1600*2200

1205 

7315 

SCB14-1250

1250 

3.4 

1500*940*1300

2000*1600*2200

1420 

8720 

SCB14-1600

1600 

3.95 

1500*940*1410

2200*1600*2200

1665 

10555 

SCB14-2000

2000 

5.1 

1650*1190*1780

2200*1600*2200

2075 

13005 

SCB14-2500

2500 

1720*1190*1800

2200*1600*2200

2450 

15445 

SC(B)14  epoxy casting dry-type transformer

 

Model number

Rated capacity
(kVA)

 VoltageCombination

Linkage group

 labeling

Impedance voltage


(%)

Transformer weight
(kg)

Transformer reference size

(mm)
L*W*H

Housing reference size(mm)
L*W*H

No-load loss
(w)

Load Loss
(w)

High Voltage(kV)

Low Voltage (kV)

SC18-30

30 

6

6.3

10

10.5

0.4

Dyn11

YynO

0.28

680*450*640

1100*850*1040

105 

640

SC18-50

50 

0.33

700*450*640

1260*850*1150

155 

900

SC18-80

80 

0.4

860*450*760

1500*1300*2200

210 

1240

SC18-100

100 

0.7

920*780*900

1500*1300*2200

230 

1415

SC18-125

125 

0.77

920*780*950

1500*1300*2200

270 

1665

SC18-160

160 

0.88

920*780*1000

1800*1300*2200

310 

1915

SC18-200

200 

1.03

1100*780*1000

1800*1300*2200

360 

2275

SC18-250

250 

1.2

1100*650*1150

1800*1300*2200

415 

2485

SC18-315

315 

1.43

1100*940*1150

1800*1300*2200

510 

3125

SCB18-400

400 

1.65

1100*940*1200

2000*1500*2200

570 

3590

SCB18-500

500 

2.1

1350*940*1200

2000*1500*2200

670 

4390

SCB18-630

630 

2.25

1350*940*1300

2000*1500*2200

775 

5290

SCB18-630

630 

2.25

1400*940*1130

2000*1500*2200

750 

5365

SCB18-800

800 

2.6

1450*940*1140

2000*1500*2200

875 

6265

SCB18-1000

1000 

3

1500*940*1250

2000*1600*2200

1020 

7315

SCB18-1250

1250 

3.4

1500*940*1300

2000*1600*2200

1205 

8720

SCB18-1600

1600 

3.95

1500*940*1410

2200*1600*2200

1415 

10555

SCB18-2000

2000 

5.1

1650*1190*1780

2200*1600*2200

1760 

13005

SCB18-2500

2500 

6

1720*1190*1800

2200*1600*2200

2080 

15445

SC(B)18  epoxy casting dry-type transformer

Product Characteristics

(1) Performance characteristics

  1. is safe, fireproof, non-polluting, and can run directly in the load center;
  2. High mechanical strength, strong short-circuit resistance, small partial discharge, good thermal stability, high reliability and long service life;
  3. Low loss, low noise, obvious energy saving effect, maintenance free;
  4. Good heat dissipation performance, strong overload capacity, and capacity increase operation when forced air cooling;
  5. good moisture-proof performance, adapted to operate in high humidity and other harsh environments;
  6. can be equipped with perfect temperature detection and protection system. Adopting intelligent signal temperature control system, it can automatically detect and itinerantly display the working temperature of each of the three-phase windings, and it can automatically start and stop the fan with alarm, trip and other function settings;
  7. small size, light weight, occupies less space, low installation cost.

(2) Structural features:

  1. iron core selection of cold rolled silicon steel sheet, 45 degree disintegration safety oblique joint structure, the use of three shear two punch core de-angled transverse shear process and five-step step shear and stacked iron process, improve the flux distribution at the joints, reducing the vibration energy of the core. The core is cured in one piece and the surface is sealed with insulating resin, which effectively reduces no-load loss, no-load current and core noise;
  2. high voltage coils are wound with copper conductors with F-class insulation and international insulating materials, and larger capacity coils are equipped with heat dissipation air channels along the axial direction. This structure has good resistance to current impact, temperature change, cracking and good heat dissipation. Adopting multi-stage segmented cylindrical structure, it has strong ability to withstand over-voltage and very low partial discharge level. The coils are molded and cast after vacuum drying, the whole casting and curing process is completed according to the pre-programmed process curve, and the precise process control ensures that the coils are free of air holes and cavities;
  3. low-voltage coils can adopt foil structure, which effectively solves the problem of ampere-turn imbalance of low-voltage and high-current coils adopting wire-winding type; meanwhile, foil coils do not have axial turns and axial winding spiral angle, which effectively eliminates the axial force of transformer during short-circuiting, and ensures that the current density inside the coil can be adjusted axially freely according to the distribution of load of high-voltage coils, and reduce the radial force during sudden low-voltage short-circuit. After winding, the coil ends are sealed and cured with resin, which avoids the entry of all kinds of foreign matter and moisture.

Key words:

10kV Dry-type Transformer

Get A Quote

Leave your contact information and get a free product quote

Solution

Become a leader in the power distribution industry in the intelligent era

Related Products

The company mainly operates transformer and distribution equipment such as screens, desks, cabinets, and boxes, as well as transformer and distribution equipment, transformers, switches, automation control systems, etc

10kV Dry-type Transformer


● Model: SC(B)12、SC(B)14、SC(B)18 ● Capacity: 30kVA to 2500kVA ● Voltage: 0.4kV, 6kV to 11kV

6.6\11kV Oil-immersed Transformer


● Voltage: 6kV to 11kV ● Capacity: 30kVA to 2500kVA

10kV Three-dimensional Rolled Iron Core Transformer


● Voltage: 400V, 6kV to 10kV ● Capacity: 30kVA to 2500kVA ● Model: S13、S20、S22

0.4\6.6\10\11kV Cast Resin Dry Type Transformer


● Voltage: 0.4kV, 6kV to 11kV ● Capacity: 30kVA to 2500kVA ● Model: SC(B)12、SC(B)14、SC(B)18

Get A Quote