Key Parameters to Consider When Purchasing a Transformer
Rated Capacity
Rated capacity is the core parameter of a transformer, directly matching power load requirements. Determine the capacity following the rule of "actual maximum load plus a 20 % expansion margin". For instance, for an actual load of 800 kVA, choose a 1000 kVA unit to prevent overload caused by insufficient capacity or waste from excessive redundancy.
Note: For scenarios with large load fluctuations (e.g. factories and charging piles), the expansion margin may be increased to 30 %; for long‑term low‑load operation (e.g. township power distribution), a 15 % margin is sufficient.

Voltage Class
Voltage class must match both the incoming grid and downstream electrical equipment; mismatching is unacceptable. Common primary‑side input voltages include 11 kV (urban distribution networks) and 35 kV (regional power transmission), while special cases cover 6 kV, 110 kV, etc. Select according to local grid specifications.
The secondary‑side output voltage is mostly 0.4 kV (three‑phase), compatible with industrial and civil electrical appliances. Custom output voltages are required for special equipment such as high‑voltage motors.
Important reminder: Voltage‑class mismatching will render equipment inoperable. Confirm grid access voltage and rated voltage of consuming equipment prior to procurement.

Winding Material
- All‑copper winding: high conductivity, low loss and long service life. Preferred for long‑term and heavy‑load applications.
- Aluminum winding: low cost yet higher loss and shorter lifespan. Only suitable for budget‑limited short‑term deployment.
- Copper‑clad aluminum winding: performance sits between the above two types. Balances cost and stability for general medium‑load scenarios.

Energy‑Efficiency Class
Energy‑efficiency class determines long‑term electricity expenses and is key to whole‑life cost‑effectiveness. National standards define Class 1, Class 2 and Class 3 energy efficiency. Oil‑immersed transformers of S11 / S13 series and dry‑type transformers of SCB14 series generally reach Class 2 or higher.
For continuous‑operation scenarios (≥ 8 hours per day), prioritize Class 1 efficiency. Though its purchase price is 5‑8 % higher, savings on electricity bills can offset the price premium within 2‑3 years. Class 2 efficiency is adequate for short‑term or low‑load conditions.
Insulation and Protection Classes
- Class F (temperature resistance: 155 ℃): baseline rating for general environments.
- Class H (temperature resistance: 180 ℃): for high‑temperature environments such as workshops and sun‑exposed outdoor locations.
.jpg)
Voltage Regulation Mode
- Off‑circuit tap‑changer: requires manual tap adjustment during power‑off (3‑5 tap positions). Cost‑effective, for sites with stable voltage where frequent regulation is unnecessary, such as residential communities and small‑scale factories.
- On‑load tap‑changer: enables automatic or remote tap‑changing without power interruption (15‑27 tap positions) with high regulation accuracy. Suitable for locations with severe voltage fluctuations and high power‑continuity requirements, e.g. data centres and industrial plants.
Cooling Method
Cooling method determines heat‑dissipation efficiency and prevents premature thermal ageing.
For oil‑immersed transformers:
- ONAN (Oil Natural Air Natural): for outdoor ambient‑temperature applications.
- ONAF (Oil Natural Air Forced): recommended for large‑capacity or high‑temperature operating conditions.
- AN (Air Natural): baseline natural air cooling.
- AF (Air Forced): for heavy‑load conditions, boosting overload capability by 30 %.
Vector Group
Vector group governs voltage phase matching to avoid abnormal equipment operation. Widely adopted configurations include Dyn11 (universal for oil‑immersed and dry‑type transformers) and Yyn0 (common for civil power distribution). Dyn11 delivers stronger tolerance to unbalanced loads, whereas Yyn0 features simpler wiring.
Select Dyn11 for industrial sites with numerous devices and unbalanced loads; Yyn0 may be adopted for civil applications with stable loads. Phase compatibility with downstream equipment must be verified.
To sum up, transformer purchasing hinges on "parameter‑to‑scenario matching".
For indoor densely‑occupied premises (hospitals, shopping malls): focus on insulation class (Class H), protection class (IP20), and all‑copper winding.
For outdoor industrial sites: emphasize protection class (IP54), air‑forced cooling, and on‑load voltage regulation.